Viessmann Vitodens 300 Service Instructions Manual page 13

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Further details regarding the individual steps
Initial start-up, inspection, maintenance
(cont.)
1. Close the gas shut-off valve.
2. Release the screw inside test nip-
ple PE A on the gas combination
valve , but do not remove, and con-
nect the pressure gauge.
3. Open the gas shut-off valve.
4. Check the static pressure; it should
be a max. of 57.5 mbar. Record the
actual value in the service report.
5. Start up boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 seconds, press E to
reset the burner.
6. Check the supply (flow) pressure; it
should be
&
20 mbar for natural gas,
&
50 mbar for LPG.
Note
Use suitable test equipment with a
resolution of at least 0.1 mbar to
measure the supply pressure.
Record the actual value in the ser-
vice report.
Take the action shown in the table.
13