Setting The Max. Output - Viessmann Vitodens 300 Service Instructions Manual

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps

Setting the max. output

Note
The max. output can be limited for heating operation. You can limit the output
via the modulation range.
1. Start up boiler.
2. Press both K and F simulta-
neously until 100 flashes on the
display, (equals 100 % of the rated
output) and A appears. On
weather-compensated control
units, the display additionally
shows "Max. output".
3. With a/b select the required
value in % of rated output as max.
output.
16
(cont.)
6. Set the upper rated output.
Constant temperature control units:
With a/b in the display, select
&
2.
Weather-compensated control
units:
With a/b in the display, select
&
"Full load".
7. Check the CO
content. Should the
2
actual value deviate by more than
1 % from the above range, imple-
ment steps from page 15 (possibly
replace the burner).
8. After testing, press d.
9. Enter actual values into the service
report.
4. Confirm the set value with d.
5. Record the settings for max. output
on the additional type plate
included with the technical docu-
mentation. Affix the type plate next
to the original type plate on top of
the boiler.
Note
The output can also be limited for
DHW loading. For this, change coding
address 6F in code 2.