Viessmann Vitodens 300 Service Instructions Manual page 41

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Code 1
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
Summer econ. M2
A5:5
*
1
With heating circuit
pump logic function
Min. flow temp. A1
C5:20
Electronic limit of the
minimum flow tempera-
ture: 20 °C
Min. flow temp. M2
C5:20
Electronic limit of the
minimum flow tempera-
ture: 20 °C
Max. flow temp. A1
C6:75
*
1
Electronic maximum
flow temperature limit at
75 °C
Max. flow. temp. M2
C6:75
*
1
Electronic maximum
flow temperature limit at
75 °C
Slope A1
d3:14
*
1
Heating curve slope =
1.4
Slope M2
d3:14
*
1
Heating curve slope =
1.4
Level A1
d4:0
*
1
Heating curve level =
0
Level M2
d4:0
*
1
Heating curve level =
0
*1
Only for weather-compensated control units.
Coding
Possible change
change
Address:
value
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 1 to 127 °C
C5:127
C5:1
Minimum limit adjustable
to
from 1 to 127 °C
C5:127
C6:1
Maximum limit adjustable
to
from 1 to 127 °C
C6:127
C6:1
Maximum limit adjustable
to
from 1 to 127 °C
C6:127
d3:2
Heating curve slope
to
adjustable from 0.2 to 3.5
d3:35
(see page 33)
d3:2
Heating curve slope
to
adjustable from 0.2 to 3.3
d3:35
(see page 33)
d4:–13
Heating curve level
adjustable from –13 to 40
to
d4:40
(see page 33)
d4:–13
Heating curve level
adjustable from –13 to 40
to
d4:40
(see page 33)
Coding
41