Viessmann Vitodens 300 Service Instructions Manual page 58

Type wb3a, 49 and 66 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
b5:0
*
1
With remote control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
*
2
tion
Parameter
With heating circuit pump logic function: Heating cir-
address b5:...
cuit pump OFF, if
1:
active RT
2:
active RT
3:
active RT
4:
active RT
5:
active RT
6:
active RT
7:
active RT
8:
active RT
Coding in
Function mode
the as
delivered
condition
Address:
value
Boiler circuit, mixer circuit
C5:20
*
1
Electronic limit of the
minimum flow tempera-
ture: 20 °C
C6:74
*
1
Electronic limit of the
maximum flow tempera-
ture: 74 °C
d3:14
*
1
Heating curve slope =
1.4
*1
Only for weather-compensated control units.
*2
Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
58
Coding
change
Address:
value
b5:1
to
b5:8
> RT
+ 5 K; passive RT
Actual
Set
> RT
+ 4 K; passive RT
Actual
Set
> RT
+ 3 K; passive RT
Actual
Set
> RT
+ 2 K; passive RT
Actual
Set
> RT
+ 1 K; passive RT
Actual
Set
> RT
; passive RT
Actual
Set
> RT
- 1 K; passive RT
Actual
Set
> RT
- 2 K; passive RT
Actual
Set
Coding
change
Address:
value
C5:1
to
C5:127
C6:0
to
C6:127
d3:2
to
Possible change
Heating circuit pump
logic function - see the
following table
< RT
+ 4 K
Actual
Set
< RT
+ 3 K
Actual
Set
< RT
+ 2 K
Actual
Set
< RT
+ 1 K
Actual
Set
< RT
Actual
Set
< RT
- 1 K
Actual
Set
< RT
- 2 K
Actual
Set
< RT
- 3 K
Actual
Set
Possible change
Minimum limit adjustable
from 1 to 127 °C
Maximum limit adjustable
from 1 to 127 °C
Heating curve slope
adjustable from 0.2 to 3.5