CPM1A Expansion I/O Unit Wiring

I/O Wiring Precautions
3-6

CPM1A Expansion I/O Unit Wiring

40-point I/O Units (CPM1A-40ED@@)
Input Wiring
To enable using the analog I/O under optimal conditions, be careful of the fol-
lowing points for noise reduction.
• Use 2-conductor shielded twisted-pair cable for the I/O wiring, and do not
connect the shield.
• Wire I/O lines apart from power lines (AC power supply lines, three-phase
power lines, etc.), and do not place them in the same duct.
• If noise is received from power supply lines (e.g., when sharing a power
supply with electric welding machines or electric charging devices, or
when near a high-frequency source), insert a noise filter in the power sup-
ply input section.
CPM1A Expansion I/O Units
Model
40-point I/O
CPM1A-40EDR
Units
CPM1A-40EDT
CPM1A-40EDT1
20-point I/O
CPM1A-20EDR1
Units
CPM1A-20EDT
CPM1A-20EDT1
16-point
CPM1A-16ER
Output Units
8-point Input
CPM1A-8ED
Units
8-point Out-
CPM1A-8ER
put Units
CPM1A-8ET
CPM1A-8ET1
For details on wiring Expansion Units, such as Analog I/O Units, Temperature
Sensor Units, CompoBus I/O Link Units, and DeviceNet I/O Link Units, refer to
SECTION 7 Using CPM1A Expansion Units and Expansion I/O Units.
24 VDC
+
+
NC
NC COM 01
03
NC
NC
00
02
04
Inputs
24 24-VDC
inputs
12 24-VDC
inputs
None
8 24-VDC
inputs
None
CIO m+1
05
07
09
11
01
06
08
10
00
02
CIO m+1
Section 3-6
Outputs
12 relay outputs
12 transistor outputs (sinking)
12 transistor outputs (sourcing)
8 relay outputs
8 transistor outputs (sinking)
8 transistor outputs (sourcing)
16 relay outputs
None
8 relay outputs
8 transistor outputs (sinking)
8 transistor outputs (sourcing)
CIO m+2
03
05
07
09
11
04
06
08
10
CIO m+2