Omron CP1H-CPU - 05-2006 Operation Manual page 457

Cp1h cpu unit
Table of Contents

Advertisement

Temperature Sensor Units
Note
!Caution Set the temperature range according to the type of temperature sensor con-
!Caution Do not set the temperature range to any values other than those for which
Setting
Input type
0
K
1
2
J
3
4 to F
---
426
DIP Switch Settings
The DIP switch is used to set the temperature unit ( C or F) and the number
of decimal places used.
ON
1
2
SW1
1
Temperature unit
2
Number of decimal
places used (See note.)
(0.01 expression)
For details on 2-decimal-place Mode, refer to Two-decimal-place Mode on
page 433.
Rotary Switch Setting
nected to the Unit. Temperature data will not be converted correctly if the tem-
perature range does not match the sensor.
temperature ranges are given in the following table. An incorrect setting may
cause operating errors.
The rotary switch is used to set the temperature range.
CPM1A-TS001/002
Range ( C)
Range ( F)
200 to 1,300
300 to 2,300
0.0 to 500.0
0.0 to 900.0
100 to 850
100 to 1,500
0.0 to 400.0
0.0 to 750.0
Cannot be set.
Setting
OFF
C
ON
F
OFF
Normal (0 or 1 digit after the decimal
point, depending on the input range)
ON
2-decimal-place Mode
CPM1A-TS101/102
Input type
Range ( C)
Pt100
200.0 to 650.0
JPt100
200.0 to 650.0
---
Cannot be set.
---
---
Section 7-5
Range ( F)
300.0 to
1,200.0
300.0 to
1,200.0