Analog I/O (XA CPU Units)
Procedure
Reading A/D Conversion
Values
Analog input device
Temperature sensor
Pressure sensor
Speed sensor
Flow sensor
Voltage/current meter
Other device
Writing D/A Conversion
Values
Ladder program
MOVE instruction
MOV
Set the Analog Input DIP Switch.
Set the PLC Setup.
Wire the I/O.
Write the ladder program.
CP1H CPU Unit
Analog input 1 conversion value
Analog input 2 conversion value
Analog input 3 conversion value
Analog input 4 conversion value
CP1H CPU Unit
Write conversion
value (SV).
• When using analog inputs, use the Analog
Voltage/Current Input Switches to set the
inputs as voltage or current inputs. (Each
input is set independently.)
• Set whether each input or output will be used.
(Each I/O point is set independently.)
• Set the I/O resolution. (The same setting is
used for all I/O points.)
• Set the analog input range:
0 to 5 V, 1 to 5 V, 0 to 10 V, or 10 to 10 V
(Each input is set independently.)
• Set the analog output range:
0 to 20 mA or 4 to 20 mA
(Each output is set independently.)
• Wire the I/O devices.
• Analog inputs: Read the conversion value.
• Analog outputs: Write the conversion value.
CIO 200
CIO 201
CIO 202
CIO 203
CIO 210
Analog output 1 SV
Analog output 2 SV
CIO 211
Section 5-5
Ladder program
MOVE instruction
MOV
Read conversion
value.
Analog output device
Adjustment equipment
Servo Controller
Variable speed device
Recorder
Other device
325