Omron CP1H-CPU - 05-2006 Operation Manual page 586

Cp1h cpu unit
Table of Contents

Advertisement

Auxiliary Area Allocations by Address
Addresses
Name
Word
Bits
A508
A508.09 Differentiate
Monitor
Completed
Flag
A508.11 Trace Trig-
ger Monitor
Flag
A508.12 Trace Com-
pleted Flag
A508.13 Trace Busy
Flag
A508.14 Trace Start
Bit
A508.15 Sampling
Start Bit
A510 to
All
startup Time These words contain the time at
A511
A512 to
All
Power Inter-
A513
ruption Time
Function
ON when the differentiate monitor
condition has been established dur-
ing execution of differentiation moni-
toring.
(This flag will be cleared to 0 when
differentiation monitoring starts.)
ON when a trigger condition is estab-
lished by the Trace Start Bit
(A508.14). OFF when the next Data
Trace is started by the Sampling
Start bit (A508.15).
ON when sampling of a region of
trace memory has been completed
during execution of a Trace.
OFF when the next time the Sam-
pling Start Bit (A508.15) is turned
ON.
ON when the Sampling Start Bit
(A508.15) is turned ON. OFF when
the trace is completed.
Turn this bit ON to establish the trig-
ger condition. The offset indicated by
the delay value (positive or negative)
determines which data samples are
valid.
When a data trace is started by turn-
ing this bit ON from the CX-Program-
mer, the PLC will begin storing data
in Trace Memory by one of the three
following methods:
1) Data is sampled at regular inter-
vals (10 to 2,550 ms).
2) Data is sampled when TRSM(045)
is executed in the program.
3) Data is sampled at the end of
every cycle.
The operation of A508.15 can be
controlled only from the CX-Pro-
grammer.
which the power was turned ON. The
contents are updated every time that
the power is turned ON. The data is
stored in BCD.
A510.00 to A510.07: Second (00 to
59)
A510.08 to A510.15: Minute (00 to
59)
A511.00 to A511.07: Hour (00 to 23)
A511.08 to A511.15: Day of month
(01 to 31)
These words contain the time at
which the power was interrupted.
The contents are updated every time
that the power is interrupted. The
data is stored in BCD.
A512.00 to A512.07: Second (00 to
59)
A512.08 to A512.15: Minute (00 to
59)
A513.00 to A513.07: Hour (00 to 23)
A513.08 to A513.15: Day of month
(01 to 31)
(These words are not cleared at star-
tup.)
Settings
Status
Status at
after
startup
mode
change
ON: Monitor
Retained Cleared
condition
established
OFF: Not yet
established
ON: Trigger
Retained Cleared
condition
established
OFF: Not yet
established or
not tracing
ON: Trace
Retained Cleared
completed
OFF: Not trac-
ing or trace in
progress
ON: Trace in
---
---
progress
OFF: Not trac-
ing (not sam-
pling)
ON: Trace trig-
---
---
ger condition
established
OFF: Not
established
OFF to ON:
---
---
Starts data
trace (sam-
pling)
Turned ON
from Program-
ming Device.
See Function
Retained See
column.
Function
column.
See Function
Retained Retained Written at
column.
Appendix D
Write
Related
timing
Flags,
Settings
---
---
---
---
---
---
---
---
---
---
---
---
Refresh-
---
ed when
power is
turned
ON.
---
power
interrup-
tion
555