Omron CP1H-CPU - 05-2006 Operation Manual page 444

Cp1h cpu unit
Table of Contents

Advertisement

Analog I/O Units
Analog Input Signal
Ranges
10 to 10 V
The 10- to 10-V range corresponds to the hexadecimal values F448 to 0BB8
( 3000 to 3000). The entire data range is F31C to 0CE4 ( 3300 to 3300).
A negative voltage is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
0CE4 (3300)
0BB8 (3000)
10V
11V
0000 (0)
0 to 10 V
The 0- to 10-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The entire data range is FED4 to 189C ( 300 to 6300). A negative
voltage is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0.5 V
0000 (0)
0 to 5 V
The 0- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0
to 6000). The entire data range is FED4 to 189C ( 300 to 6300). A negative
voltage is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0.25 V
0000 (0)
10 V 11 V
0 V
F448 ( 3000)
F31C ( 3300)
10 V 10.5 V
0 V
FED4 ( 300)
0 V
5 V 5.25 V
FED4 ( 300)
Section 7-4
413

Advertisement

Table of Contents
loading

Table of Contents