Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A402
A402.06 Special I/O
Unit Error Flag
(non-fatal
error)
A402.07 CPU Bus Unit
Error Flag
(non-fatal
error)
A402.10 PLC Setup
Error Flag
(non-fatal
error)
A402.13 Interrupt Task
Error Flag
(non-fatal
error)
A402.15 FAL Error Flag
(non-fatal
error)
Function
ON when an error occurs in a data
exchange between the CPU Unit and
a Special I/O Unit (including an error
in the Special I/O Unit itself).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash. The
Special I/O Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A418 through A423.
(This flag will be turned OFF when
the error is cleared.)
ON when an error occurs in a data
exchange between the CPU Unit and
an CPU Bus Unit (including an error
in the CPU Bus Unit itself).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash. The
CPU Bus Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A417.
(This flag will be turned OFF when
the error is cleared.)
ON when there is a setting error in
the PLC Setup. The CPU Unit will
continue operating and the ERR/
ALM indicator on the front of the
CPU Unit will flash. The location of
the error will be written to A406.
(This flag will be turned OFF when
the error is cleared.)
ON when the Detect Interrupt Task
Errors setting in the PLC Setup is set
to "Detect" and an interrupt task is
executed for more than 10 ms during
I/O refreshing of a Special I/O Unit.
This flag will also be turned ON if an
attempt is made to refresh a Special
I/O Unit's I/O from an interrupt task
with IORF(097) while the Unit's I/O is
being refreshed by cyclic I/O refresh-
ing (duplicate refreshing).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(This flag will be turned OFF when
the error is cleared.)
ON when a non-fatal error is gener-
ated by executing FAL(006). The
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
The bit in A360 to A391 that corre-
sponds to the FAL number specified
in FALS(006) will be turned ON and
the corresponding error code will be
written to A400. Error codes 4101 to
42FF correspond to FAL numbers
001 to 2FF (0 to 511).
(This flag will be turned OFF when
the error is cleared.)
Settings
Status
Status
after
at star-
mode
change
ON: Error in
Cleared
Cleared
one or more
Units
OFF: No
errors in any
Unit
ON: Error in
Cleared
Cleared
one or more
Units
OFF: No error
in any Unit
ON: Error
Cleared
Cleared
OFF: No error
ON: Interrupt
Cleared
Cleared
task error
OFF: No error
ON:
Cleared
Cleared
FALS(006)
error occurred
OFF:
FALS(006)
not executed
Appendix D
Write
Related
timing
flags, set-
tup
tings
Refreshed
A418 to
when error
A423
occurs.
Refreshed
A417
when error
occurs.
Refreshed
A406
when error
occurs.
Refreshed
A426,
when error
PLC
occurs.
Setup
(Detect
Interrupt
Task
Errors set-
ting)
Refreshed
A360 to
when error
A391,
occurs.
A400