Omron CP1H-CPU - 05-2006 Operation Manual page 583

Cp1h cpu unit
Table of Contents

Advertisement

Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A426
A426.00
Interrupt Task
to
Error, Unit
A426.11
Number
A426.15 Interrupt Task
Error Cause
Flag
A434
A434.00
Built-in Ana-
to
log Input Error
A434.03
Details
A434.04 Analog Initial-
ization Com-
pleted Flag
A436
A436.00
CPM1A Unit
to
Error Flags
A436.06
A437
All
Number of
Connected
CPM1A Units
A438
All
Pulse Output
2 Stop Error
Code
552
Function
An attempt was made to refresh a
Special I/O Unit's I/O from an inter-
rupt task with IORF(097) while the
Unit's I/O is being refreshed by cyclic
I/O refreshing (duplicate refreshing).
A426.00 to A426.11 contain the Spe-
cial I/O Unit's unit number.
These bits will be cleared when the
error is cleared.
When A402.13 (the Interrupt Task
Error Flag) is ON, this flag indicates
the cause of the error. The CPU Unit
will continue operating and the ERR/
ALM indicator on the front of the
CPU Unit will flash.
This flag turns ON when an attempt
is made to refresh a Special I/O Unit
during an interrupt task while the
Unit is being refreshed in cyclic pro-
cessing.
ON when an error occurs in a built-in
analog input.
A434.00: Analog Input 0 Open-circuit
Error Flag
A434.01: Analog Input 1 Open-circuit
Error Flag
A434.02: Analog Input 2 Open-circuit
Error Flag
A434.03: Analog Input 3 Open-circuit
Error Flag
ON while the built-in analog I/O is
being initialized.
ON when an error occurs in a
CPM1A Expansion Unit or Expan-
sion I/O Unit.
A436.00: 1st Unit
A436.10: 2nd Unit
A436.02: 3rd Unit
A436.03: 4th Unit
A436.04: 5th Unit
A436.05: 6th Unit
A436.06: 7th Unit
Stores the number of CPM1A Expan-
sion Units and Expansion I/O Units
connected as a hexadecimal num-
ber.
Note This information is valid only
when a Too Many I/O Points
error has occurred. CPM1A-
TS002 and CPM1A-TS102
are each counted as two
Units.
If a Pulse Output Stop Error occurs
for pulse output 2, the error code is
stored.
Settings
Status
Status
after
at star-
mode
change
Unit number:
Cleared
Cleared
000 to 05F
(0 to 95)
ON: Dupli-
Cleared
Cleared
cated refresh-
ing
OFF: No error
Retained Cleared
ON: Error
OFF: Initializ-
ing
ON: Initializa-
tion com-
pleted
OFF: No error
Retained Cleared
ON: Error
0000 to 0007
Retained Cleared
hex
---
Retained Cleared
Appendix D
Write
Related
timing
flags, set-
tup
tings
---
A402.13
A426.15
---
A402.13,
A426.00
to
A426.11
When
---
open-cir-
cuit is
detected.
---
---
---
---
Refreshed
---
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.

Advertisement

Table of Contents
loading