Error Reset

12-6 Error Reset
12-6-1 Resetting Unit Common Errors
Common Operating Memory Area (Output)
Common Operating Memory Area (Input)
506
The PCU indicates Unit common errors and individual axis errors in the Com-
mon Operating Memory Area and Axis Operating Input Memory Areas,
respectively, using Error Flags and error codes.
These errors can be cleared by removing the cause of the error and executing
ERROR RESET.
The methods for resetting Unit common errors and individual axis errors are
different.
Unit common errors are cleared by turning ON (
Bit in the Common Operating Memory Area.
Reset Unit common errors when the Unit Busy Flag for the Position Control
Unit is OFF. If errors are reset when the Unit Busy Flag is ON, a multistart
error (Unit error code: 0021) will occur and it will not be possible to reset Unit
common errors.
When clearing Unit common errors, make sure that the UNIT ERROR RESET
Bit in the Common Operating Memory Area remains ON until the Unit Busy
Flag turns ON.
Name
Word
UNIT ERROR
n
RESET Bit
n = CIO 1500 + (unit number × 25)
Name
Word
Unit Error Flag
n+15
Unit Busy Flag
n+16
Unit error code
n+21
n = CIO 1500 + (unit number × 25)
Timing Chart Example for UNIT ERROR RESET
UNIT ERROR RESET Bit
(word n, bit 00)
Unit Error Flag
(word n+15, bit 12)
Unit Busy Flag
(word n+16, bit 14)
Unit Error Code
0000
(word n +21)
(Example) Multistart Error
n = CIO 1500 + (unit number × 25)
) the UNIT ERROR RESET
Bit
00
: Resets Unit common error
Bit
12
0: Unit common error has not occurred.
1: Unit common error has occurred.
14
0: PCU is not busy
1: PCU is busy
---
Stores the error code when a Unit common
error occurs.
The Unit Busy Flag remains ON
for at least one cycle time when
UNIT ERROR RESET is
0021 hex
0000
executed.