7.8 Set functions related to protection and warning, each output signal

7.8.1 Trip signal (AL)

When it detects an anomaly, the inverter output is shut off, the inverter outputs a trip signal.
This is called a trip.
If you reset, the inverter deactivate trip state. Trip signal is turned OFF at the same time.
How to Reset.
1) Pressing the STOP/RESET key.
2) To use the reset terminal (18:RS).
(Part of the cause of trip can not be released by a reset. In this case, it is required a power cycle.)
Trip signal(05:AL) is assigned to the output terminal 11(C021) or Alarm relay (C026).
(Initial data C026 = 05[AL])
Alarm relay contacts are 1c.(Refer to 7.3.5)
Item
Output [11] function
Alarm relay function
Terminal [1] to [5] functions
Run command
(FW,RV)
Rotational speed
Reset signal
AL signal
Occurrence of a trip
Function code
C021
C026
C001 to C005
Occurrence of a trip
RUN
RUN
STOP
RESET
Rest
RUN
STOP
RESET
STOP
RUN
STOP
RESET
Reset
Trip
7 - 60
Data
05
AL : Trip signal
18
RS : Reset signal
Free-run
Run
Occurrence of a trip
Description