Logical Output Signal Operation Function (Log1 To Log6) - Hitachi SJ700-4000HFU2 Instruction Manual

Hide thumbs Also See for SJ700-4000HFU2:
Table of Contents

Advertisement

Chapter 4
Intelligent output terminals
14
13
12
11
AC3
AC2
AC1
AC0
1
1
0
1
1
1
1
0
1
1
1
1
Item
Alarm code output

4.2.66 Logical output signal operation function (LOG1 to LOG6)

The logical output signal operation function allows you to make the
inverter internally perform a logical operation of output signals.
This function applies to all output signals, except to logical operation
results (LOG1 to LOG6).
Three types of operators (AND, OR, and XOR) are selectable.
Output signal 1
Output signal 2
LOGx (AND)
LOGx (OR)
LOGx (XOR)
The necessary parameters depend on the logical output signal to be operated. The following table lists the parameters
to be set for each logical output signal:
Selected signal
33: Logical output signal 1 (LOG1)
34: Logical output signal 2 (LOG2)
35: Logical output signal 3 (LOG3)
36: Logical output signal 4 (LOG4)
37: Logical output signal 5 (LOG5)
38: Logical output signal 6 (LOG6)
(Example)
To output the AND of the running signal (00: RUN) and set the frequency overreached signal (02: FA2) as
the logical output signal 1 (LOG1) to the intelligent output terminal [2]:
- Intelligent output terminal [2] (C002): 33 (LOG1)
- Logical output signal 1 selection 1 (C142): 00 (RUN)
- Logical output signal 1 selection 2 (C143): 02 (FA2)
- Logical output signal 1 operator (C143): 00 (AND)
When "4 bits" is selected
Factor code
Cause of tripping
Temperature error due to low
E20, E21
cooling-fan speed
Temperature error
E24
Phase loss input protection
Easy sequence user trip 0-9,
E50 to E79
option 1,2 error 0-9
Function code
C062
Operation-target 1
selection
C142
C145
C148
C151
C154
C157
Explanation of Functions
Factor code
Data
00
No output of alarm code
01
Output of 3-bit code
02
Output of 4-bit code
Related code
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C142: Logical output signal 1 selection 1
C143: Logical output signal 1 selection 2
C144: Logical output signal 1 operator selection
C145: Logical output signal 2 selection 1
C146: Logical output signal 2 selection 2
C147: Logical output signal 2 operator selection
C148: Logical output signal 3 selection 1
C149: Logical output signal 3 selection 2
C150: Logical output signal 3 operator selection
C151: Logical output signal 4 selection 1
C152: Logical output signal 4 selection 2
C153: Logical output signal 4 operator selection
C154: Logical output signal 5 selection 1
C155: Logical output signal 5 selection 2
C156: Logical output signal 5 operator selection
C157: Logical output signal 6 selection 1
C158: Logical output signal 6 selection 2
C159: Logical output signal 6 operator selection
Operation-target 2
selection
C143
C146
C149
C152
C155
C158
4-66
When "3 bits" is selected
Cause of tripping
Description
Operator
selection
C144
C147
C150
C153
C156
C159

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sj700d-3 series

Table of Contents