Daikin VRV EMERION RXYQ-AATJA Service Manual page 389

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
Thermistor temperature
(°C)
(°F)
–30
–22
–25
–13
–20
–4
–15
5
–10
14
–5
23
0
32
5
41
10
50
15
59
20
68
25
77
30
86
35
95
40
104
45
113
50
122
55
131
60
140
65
149
70
158
75
167
80
176
85
185
90
194
95
203
100
212
105
221
Drawing No.
Part 6 Service Diagnosis
Type A
363.8
266.8
197.8
148.2
112.0
85.52
65.84
51.05
39.91
31.44
24.95
19.94
16.04
12.99
10.58
8.669
7.143
5.918
4.928
4.123
3.467
3SA48002
3SA48018
3SA48019
(AD94A045)
3SA48013
(AD100026)
Resistance (k)
Type B
111.1
84.95
65.53
50.95
39.92
31.50
25.02
20.00
16.10
13.04
10.63
8.720
7.189
3SA48001
(AD210486)
This data is for reference purposes only.
Check
Type C
111.8
85.42
65.80
51.07
39.97
31.51
25.02
20.00
16.10
13.04
10.63
8.711
7.179
3SA48016
(AD100008)
382