Daikin VRV EMERION RXYQ-AATJA Service Manual page 361

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
Part 6 Service Diagnosis
Diagnosis Flowchart-6
U7-07
Error code
Sub code
(Connection 4 or more outdoor units
to the same system)
4 or more outdoor
units are connected using
the outdoor unit multi
transmission
wirings.
YES
Diagnosis Flowchart-7
U7-11
Error code
Sub code
(Connection of excess indoor units
for test operation)
There is
an error in the
connection of
indoor-outdoor, indoor-indoor, and
outdoor multi transmission
wirings.
NO
The capacity to
connect indoor units
falls within the specified
range.
YES
Troubleshooting by Error Code
NO
Replace the outdoor unit main
PCB (A1P).
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
YES
Rectify the error in the connection
of transmission wirings, and then
reset the power supply.
NO
Check the capacity to connect
indoor units.
Replace the outdoor unit main
PCB (A1P).
354