Outdoor Unit Rotation - Daikin VRV EMERION RXYQ-AATJA Service Manual

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Special Control
7.4

Outdoor Unit Rotation

In the case of multi outdoor unit system, this outdoor unit rotation prevents the compressor from
breaking down due to unbalanced oil level between outdoor units.
Details of outdoor unit rotation
In the case of multi outdoor unit system, each outdoor unit is given an operating priority for the
control.
The operating priority of outdoor units is changed by outdoor unit rotation. The outdoor unit rotation
prevents unbalanced oil level between outdoor units by eliminating the long stop of compressors
during partial load.
Timing of outdoor unit rotation
 At the beginning of the startup control, or;
 After oil return operation, or;
 After defrost operation, or;
 One of the outdoor units is stopped for 20 minutes or more.
Example) The following diagram shows outdoor unit rotation.
Startup control
Master
Outdoor unit
Priority
rotation
A
Master
Priority
Note(s)
 Master unit and sub unit in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are different
from master unit and sub unit for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be designated
as master unit.
Consequently, the LED display on the outdoor unit main PCB for master unit, sub unit does not
change.
119
Oil return operation
or defrost operation
Normal control
Sub
Priority
1
2
Normal control
Sub
Priority
2
1
Normal control
Master
Outdoor unit
Priority
rotation
2
Any of outdoor
unit stops for a
period of 20
minutes or more.
Normal control
Outdoor unit
rotation
SiUS342303E
Sub
Priority
1
Master
Sub
Priority
Priority
1
2
Part 4 Functions and Control