Daikin VRV EMERION RXYQ-AATJA Service Manual page 182

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Field Settings for Indoor Unit
1.4.30 Mold Proof Operation Setting (for FXEQ-P models)
Mode
14 (24)
Areas with average humidity over 80%.
1.4.31 Gas Furnace Test Mode (for CXTQ-TA models)
This setting is used for gas furnace test run.
For details, refer to Gas Furnace Test Operation on page 222.
1.4.32 Drain Pump Operation Settings (for FXMQ-PB models)
The drain pump operation can be disabled for natural drainage by changing the following field
setting.
Mode
15 (25)
1.4.33 Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20°C (68°F)
or above and turns OFF the humidifier if suction air temperature is 18°C (64.4°F) or below when the
heating thermostat is OFF.
Mode
15 (25)
1.4.34 Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. If the second code is set to
02: Equipped, energy recovery ventilator fan conducts the fan residual operation by linking to
indoor unit. The indoor fan carries out residual operation for one minute after the thermostat is
stopped. (For the purpose of preventing dust on the air filter from falling off.)
Mode
15 (25)
175
First Code
Second Code
No.
No.
No.
01
9
02
03
Mode No.
First Code No.
14 (24)
11
First Code
Second Code
No.
No.
No.
01
0
02
03
First Code
Second Code
No.
No.
No.
01
1
02
First Code
Second Code
No.
No.
No.
01
2
02
Contents
Standard
For high humidity areas ()
Second Code No.
01
02
03
Contents
ON
OFF
Contents
Not equipped
Equipped
Contents
Not equipped
Equipped
Part 5 Field Settings and Test Operation
SiUS342303E
: Factory setting
: Factory setting
Contents
OFF
Low heat
High heat
: Factory setting
: Factory setting
: Factory setting