Daikin VRV EMERION RXYQ-AATJA Service Manual page 390

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Check
Thermistor temperature
(°C)
(°F)
–30
–22
–25
–13
–20
–4
–15
5
–10
14
–5
23
0
32
5
41
10
50
15
59
20
68
25
77
30
86
35
95
40
104
45
113
50
122
55
131
60
140
65
149
70
158
75
167
80
176
85
185
90
194
95
203
100
212
105
221
110
230
115
239
120
248
125
257
130
266
135
275
140
284
145
293
150
302
Drawing No.
383
Type H
3407
2540
1910
1449
1108
853.8
662.7
517.9
407.4
322.5
256.9
205.7
165.7
134.3
109.4
89.58
73.73
60.98
50.67
42.29
35.45
29.84
25.21
21.38
18.21
15.57
13.36
11.49
9.92
8.594
7.465
6.499
5.675
4.968
4.360
3.836
3.384
3SA48006
(AD190115)
Resistance (k)
Type J
352.1
261.2
195.4
147.3
111.8
85.49
65.80
51.15
40.08
31.64
25.16
20.14
16.23
13.16
10.73
8.800
7.255
6.012
5.010
4.196
3.532
2.987
2.538
2.166
1.857
1.598
1.380
1.196
1.041
0.908
0.795
0.698
0.615
0.543
0.481
0.428
0.381
3SA48005
(AD190114)
This data is for reference purposes only.
SiUS342303E
Type N
363.4
266.7
197.8
148.2
112.1
85.51
65.80
51.11
40.01
31.54
25.04
20.00
16.09
13.02
10.60
8.685
7.153
5.923
4.929
4.122
3.463
3S480024
(AD180053)
Part 6 Service Diagnosis