Daikin VRV EMERION RXYQ-AATJA Service Manual page 121

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
Radiation Fin
Perform the following control of integrated as well as multi units for each compressor.
Temperature
Control
Condition
RXYQ72AATJA
more than
A
103°C (217°F)
less than
B
100°C (212°F)
more than
C
108°C (226°F)
Condition
RXYQ72AAYDA
more than
A
109°C (228°F)
less than
B
106°C (223°F)
more than
C
114°C (237°F)
Part 4 Functions and Control
Normal operation
A
Reduce compressor capacity
Fin temperature standby
RXYQ96/120AATJA
M1C
M2C
more than
more than
100°C (212°F)
100°C (212°F)
less than
less than
97°C (207°F)
97°C (207°F)
more than
more than
103°C (217°F)
103°C (217°F)
RXYQ96/120AAYDA
M1C
M2C
more than
more than
109°C (228°F)
109°C (228°F)
less than
less than
106°C (223°F)
106°C (223°F)
more than
more than
114°C (237°F)
114°C (237°F)
B
C
When occurring 4 times within 60
minutes, the error code L4 is output.
RXYQ144/168AATJA
M1C
more than
more than
100°C (212°F)
103°C (217°F)
less than
less than
97°C (207°F)
100°C (212°F)
more than
more than
103°C (217°F)
108°C (226°F)
RXYQ144/168AAYDA
M1C
more than
more than
109°C (228°F)
109°C (228°F)
less than
less than
106°C (223°F)
106°C (223°F)
more than
more than
114°C (237°F)
114°C (237°F)
Protection Control
RXYQ192/216/240AATJA
M2C
M1C
more than
103°C (217°F)
less than
100°C (212°F)
more than
108°C (226°F)
RXYQ192/216/240AAYDA
M2C
M1C
more than
109°C (228°F)
less than
106°C (223°F)
more than
114°C (237°F)
M2C
more than
103°C (217°F)
less than
100°C (212°F)
more than
108°C (226°F)
M2C
more than
109°C (228°F)
less than
106°C (223°F)
more than
114°C (237°F)
114