Daikin VRV EMERION RXYQ-AATJA Service Manual page 205

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
[2-25]:
[2-26]:
This setting is used in conjunction with setting [2-22].
[2-27]:
This setting is used in conjunction with setting [2-22].
Part 5 Field Settings and Test Operation
Night-time low noise operation level via the external control adaptor
If the system needs to run under night-time low noise operation conditions when an
external signal is sent to the unit, this setting defines the level of night-time low noise
that will be applied (3: Level 3 < 2: Level 2 < 1: Level 1).
This setting will only be effective when the optional external control adaptor
(DTA104A62) is installed and the setting [2-12] is activated.
Default value: 2
Change [2-25] to 1, 2 or 3 in function of required level.
Night-time low noise operation start time
Change [2-26] to 1, 2 or 3 in function of required timing.
Default value: 2
Value
Start time automatic night-time low noise
[2-26]
1
2 (default)
3
Night-time low noise operation stop time
Default value: 3
Value
Stop time automatic night-time low noise
[2-27]
1
2
3 (default)
operation (approximately)
About 8:00 PM
About 10:00 PM
About 12:00 AM
operation (approximately)
About 6:00 AM
About 7:00 AM
About 8:00 AM
Field Setting from Outdoor Unit
198

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion rxyq-aayda

Table of Contents