Compressor Step Control - Daikin VRV EMERION RXYQ-AATJA Service Manual

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Basic Control
5.3

Compressor Step Control

The compressor operation varies in the following steps according to information in Compressor PI
Control. Refer to page 104.
Depending on the operating conditions of compressors, the compressors may run in patterns other
than the following.
RXYQ72AA
Step
Step
rps
No.
No.
1
15.0
67
2
15.2
68
3
15.4
69
4
15.6
70
5
15.9
71
6
16.2
72
7
16.5
73
8
16.8
74
9
17.1
75
10
17.4
76
11
17.7
77
12
18.0
78
13
18.3
79
14
18.6
80
15
19.0
81
16
19.4
82
17
19.8
83
18
20.1
84
19
20.5
85
20
20.7
86
21
21.0
87
22
21.3
88
23
21.6
89
24
21.9
90
25
22.2
91
26
22.5
92
27
22.9
93
28
23.2
94
29
23.5
95
30
23.8
96
31
24.2
97
32
24.5
98
33
24.9
99
34
25.2
100
35
25.5
101
36
25.9
102
37
26.3
103
38
26.6
104
39
27.0
105
40
27.4
106
41
27.8
107
42
28.1
108
43
28.5
109
44
29.0
110
45
29.4
111
46
29.8
112
47
30.2
113
48
30.6
114
49
31.0
115
50
31.5
116
51
31.9
117
52
32.4
118
53
32.8
119
54
33.3
120
55
33.8
121
56
34.2
122
57
34.7
123
58
35.2
124
59
35.7
125
60
36.2
126
61
36.7
127
62
37.2
128
63
37.7
129
64
38.3
130
65
38.8
131
66
39.3
132
105
Step
rps
rps
No.
39.9
133
99.9
40.5
134
101.3
41.0
135
102.7
41.6
136
104.2
42.2
137
105.6
42.8
138
107.1
43.4
139
108.6
44.0
140
110.1
44.6
141
111.7
45.2
142
113.2
45.8
143
114.8
46.5
144
117.9
47.1
145
118.0
47.8
146
119.7
48.5
49.1
49.8
50.5
51.2
52.0
52.7
53.4
54.2
54.9
55.7
56.5
57.3
58.1
58.9
59.7
60.5
61.4
62.3
63.1
64.0
64.9
65.8
66.8
67.7
68.6
69.6
70.6
71.6
72.6
73.6
74.6
75.7
76.7
77.8
78.9
80.0
81.1
82.2
83.4
84.5
85.7
86.9
88.1
←RXYQ72AA Cooling upper limit
89.4
90.6
91.9
93.2
94.5
95.8
97.2
98.5
←RXYQ72AA Heating upper limit
SiUS342303E