Troubleshooting by Error Code
3.3

Prediction Codes

Prediction Code List
Seven-segment display
10A-##
_ _ 1
0 0 1
- # #
12A-##
_ _ 1
2 0 1
- # #
12D-##
_ _ 1
2 0 4
- # #
14A-##
_ _ 1
4 0 1
- # #
14B-##
_ _ 1
4 0 2
- # #
16A-##
_ _ 1
6 0 1
- # #
16B-##
_ _ 1
6 0 2
- # #
16C-##
_ _ 1
6 0 3
- # #
16D-##
_ _ 1
6 0 4
- # #
16E-##
_ _ 1
6 0 5
- # #
16G-##
_ _ 1
6 0 7
- # #
16H-##
_ _ 1
6 0 8
- # #
16I-##
_ _ 1
6 0 9
- # #
16J-##
_ _ 1
6 1 0
- # #
16L-##
_ _ 1
6 1 2
- # #
16P-##
_ _ 1
6 1 6
- # #
16Q-##
_ _ 1
6 1 7
- # #
16S-##
_ _ 1
6 1 9
- # #
16U-##
_ _ 1
6 2 1
- # #
16V-##
_ _ 1
6 2 2
- # #
16W-##
_ _ 1
6 2 3
- # #
20A-##
_ _ 2
0 0 1
- # #
30A-##
_ _ 3
0 0 1
# # #
31A-##
_ _ 3
1 0 1
# # #
245
Description
Compressor overcurrent prediction
EVM1 refrigerant leakage prediction
(during evaporation)
EVM2 refrigerant leakage prediction
(during evaporation)
Four way valve (20SA1) intermediate
stop prediction
Four way valve (20SA1) switching
failure prediction
Discharge pipe thermistor failure
prediction (Tdi)
Compressor body thermistor failure
prediction (Ti)
Outdoor air thermistor failure
prediction (Ta)
Heat exchanger deicer thermistor
failure prediction (Tb1)
Heat exchanger deicer thermistor
failure prediction (Tb2)
Subcooling gas pipe thermistor failure
prediction (Tsh)
Subcooling liquid pipe thermistor
failure prediction (Tsc)
Heat exchanger liquid pipe thermistor
1 failure prediction (Tf1)
Heat exchanger liquid pipe thermistor
2 failure prediction (Tf2)
Compressor suction thermistor failure
prediction (Ts)
Heat exchanger gas pipe thermistor 1
failure prediction (Tg1)
Heat exchanger gas pipe thermistor 2
failure prediction (Tg2)
Subcooling injection thermistor failure
prediction (Tm)
Electrical box air outlet thermistor
failure prediction (Tjeva)
High pressure sensor failure
prediction (HP)
Low pressure sensor failure prediction
(LP)
Heat exchanger freeze up prediction
Indoor unit electronic expansion valve
leak (evaporator) prediction
_ _ #
Indoor unit thermistor failure
_ _ #
prediction (Th1)
Possible cause
Error code L5, L8
Refer to L5, L8 troubleshooting
Same as L8
■ Ts sensor failure
Ts: Refer to J5 troubleshooting.
■ Tg sensor failure
Tg: Refer to J6 troubleshooting.
■ LP sensor failure
LP: Refer to JC troubleshooting.
■ EVM1 coil failure
Electronic expansion valve coil: Refer to E9
■ EVM1 failure
troubleshooting
If the above error is not seen, replace EVM1.
■ Ts sensor failure
Ts: Refer to J5 troubleshooting.
■ Tg sensor failure
Tg: Refer to J6 troubleshooting.
■ LP sensor failure
LP: Refer to JC troubleshooting.
■ EVM2 coil failure
Electronic expansion valve coil: Refer to E9
■ EVM2 failure
troubleshooting
If the above error is not seen, replace EVM2.
■ HP sensor failure
HP: Refer to JA troubleshooting.
■ LP sensor failure
LP: Refer to JC troubleshooting.
■ Four way valve coil failure
If the above error is not seen, compressor, four
■ Four way valve failure
way valve coil, or four way valve is defective.
■ HP sensor failure
HP: Refer to JA troubleshooting.
■ LP sensor failure
LP: Refer to JC troubleshooting.
■ Tg sensor failure
Tg: Refer to J6 troubleshooting.
■ Tf sensor failure
Tf: Refer to J8 troubleshooting.
■ Ta sensor failure
Ta: Refer to H9 troubleshooting.
■ Four way valve coil failure
If the above error is not seen, compressor, four
■ Four way valve failure
way valve coil, or four way valve is defective.
■ Tdi sensor failure
Refer to J3 troubleshooting.
■ Ti sensor failure
Refer to J3 troubleshooting.
■ Ta sensor failure
Refer to H9 troubleshooting.
■ Tb sensor failure
Refer to J6 troubleshooting.
■ Tb2 sensor failure
Refer to J6 troubleshooting.
■ Tsh sensor failure
Refer to J9 troubleshooting.
■ Tsc sensor failure
Refer to J7 troubleshooting.
■ Tf1 sensor failure
Refer to J8 troubleshooting.
■ Tf2 sensor failure
Refer to J8 troubleshooting.
■ Ts sensor failure
Refer to J5 troubleshooting.
■ Tg1 sensor failure
Refer to J6 troubleshooting.
■ Tg2 sensor failure
Refer to J6 troubleshooting.
■ Tm sensor failure
Refer to J7 troubleshooting.
■ Tjeva sensor failure
Refer to J9 troubleshooting.
■ HP sensor failure
Refer to JA troubleshooting.
■ LP sensor failure
Refer to JC troubleshooting.
■ Tb sensor failure
Melt frost on the outdoor heat exchanger.
■ Freeze
■ Tb sensor failure
Th1: Refer to C9 troubleshooting.
■ Indoor leakage
Th2: Refer to C4 troubleshooting.
Th3: Refer to C5 troubleshooting.
LP: Refer to JC troubleshooting.
If the above error is not seen, the corresponding
indoor electronic expansion valve and expansion
valve coil can be considered.
■ Th1 sensor failure
Th1: Refer to C9 troubleshooting.
■ Th2 sensor failure
Th2: Refer to C4 troubleshooting.
■ Th3 sensor failure
Th3: Refer to C5 troubleshooting.