SiUS342303E
3.16 Electronic Expansion Valve Coil Abnormality, Dust
Clogging
Applicable
All indoor unit models
Models
A9
Error Code
Method of Error
Check coil condition of electronic expansion valve by using microcomputer.
Detection
Check dust clogging condition of electronic expansion valve main body by using microcomputer.
Error Decision
Pin input for electronic expansion valve coil is abnormal when initializing microcomputer.
Conditions
Either of the following conditions is seen/caused/occurs while the unit stops operation.
R1T – R2T > 8°C (14.4°F)
R2T shows fixed degrees or below.
R1T: temperature of suction air
R2T: temperature of liquid pipe of heat exchanger
Supposed
Defective electronic expansion valve coil
Causes
Defective indoor unit control PCB
Defective relay cables
Troubleshooting
Reference
CHECK 18 Refer to page 390.
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Error
code is displayed
NO
when power is supplied
to the indoor
unit?
YES
Electronic
expansion valve is
NO
connected to X7A of
indoor unit control
PCB.
YES
Check
of electronic
NO
expansion valve coil
indicates normal.
CHECK 18
YES
Relay
YES
cables short circuit or
disconnected.
NO
Troubleshooting by Error Code
Replace the electronic
expansion valve main body.
Shut the power supply OFF
after connection and then
restart.
Replace the electronic
expansion valve coil (Y1E).
Replace the relay cables.
When restarting the operation
after shutting the power supply
OFF does not work, replace the
indoor unit control PCB (A1P).