SiUS342303E
[2-81]:
Change [2-81] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8].
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 215.
[2-82]:
Change [2-82] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 215.
[2-83]:
[2-87]:
Part 5 Field Settings and Test Operation
Cooling comfort setting
Default value: 1
Value
[2-81]
0
1 (default)
2
3
Heating comfort setting
Default value: 1.
Value
[2-82]
0
1 (default)
2
3
Master user interface allocation in case VRV indoor units and Mini-split indoor units
are used at the same time
By changing setting [2-83], you can allow the VRV indoor unit to be the operation
mode selector (system power OFF/ON is required after applying this setting).
Default value: 1
Value
[2-83]
0
VRV indoor unit has mode selection right
1 (default)
Mini-split indoor unit has mode selection right
Intermittent fan operation
Outdoor fan speed would be increased for assisting to discharge snow on outdoor
fan when outdoor fan is stop or low speed.
Default value: 0.
Value
[2-87]
0 (default)
1
30 minutes OFF, 1 minute ON with medium fan speed
2
30 minutes OFF, 1 minute ON with high fan speed
Cooling comfort setting
Eco
Mild
Quick
Powerful
Heating comfort setting
Eco
Mild
Quick
Powerful
Master user interface allocation
Intermittent fan operation
OFF
Field Setting from Outdoor Unit