Daikin VRV EMERION RXYQ-AATJA Service Manual page 200

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Field Setting from Outdoor Unit
No.
Item
1
VRTsmart
Used to change lower limit of target
control
condensation temperature in
Tc lower limit
VRTsmart control.
77
VRT control
Used to change upper limit of
78
Te upper limit
target evaporation temperature in
VRT control.
VRT control
Used to change lower limit of target
79
Tc lower limit
condensation temperature in VRT
control.
Cooling comfort
Cooling comfort setting
setting
81
Heating comfort
Heating comfort setting
setting
82
Master user
By changing this setting, you can
interface
allow the VRV indoor unit to be the
allocation in
operation mode selector (system
case VRV indoor
power OFF/ON is required after
83
units and
applying this setting).
Mini-split indoor
units are used at
the same time
Intermittent fan
Used for intermittent fan operation
operation
setting.
87
Indoor unit
Multi-tenant function setting
without power
90
1: Numbers in the "No." column represent the number of times to press the BS button.
: Setting does not return to factory setting when exit mode 2. To cancel the function, change
: Once function is activated t01 appears. To stop current function, press once the RETURN
193
Description
setting manually to factory setting.
(BS3) button. For detailed description about each setting, refer to Details of Setting Mode 2
on page 194.
Indication bold underline means factory setting.
7 segment
display
SEG
SEG
SEG
1
2
3
Low
Standard
High 1
High 2
2.
7
7
High 3
High 4
High 5
High 6
Standard
2.
7
8
High
Standard
2.
7
9
Low
Eco
Mild
2.
8
1
Quick
Powerful
Eco
Mild
2.
8
2
Quick
Powerful
VRV indoor unit has mode
selection right
Mini-split indoor unit has
mode selection right
2.
8
3
OFF
30 minutes OFF, 1 minute ON
2.
8
7
with medium fan speed
30 minutes OFF, 1 minute ON
with high fan speed
Invalid
Valid (No U4 error generation)
2.
9
0
Valid (Operating with U4
warning)
SiUS342303E
7 segment
Description
SEG
1
Part 5 Field Settings and Test Operation
display
Range
SEG
SEG
2
3
0
1
2
3
4
5
6
7
4
6
2
3
0
1
2
3
0
1
2
3
0
1
0
1
2
0
1
2