Daikin VRV EMERION RXYQ-AATJA Service Manual page 198

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Field Setting from Outdoor Unit
No.
Item
1
External low
Low noise level when the external
25
noise level
low noise signal is input at option
DTA104A62.
Automatic night-
Time to start automatic "night-time
time low noise
low noise" operation. ("Night-time
26
operation start
low noise" level setting should also
be made.)
Automatic night-
Time to stop automatic "night-time
time low noise
low noise" operation. ("Night-time
27
operation stop
low noise" level setting should also
be made.)
Power transistor
Used to troubleshoot DC
check
compressor. Inverter waveforms
are output without wire connections
28
to the compressor. It is useful to
determine whether the relevant
trouble has resulted from the
compressor or inverter PCB.
Capacity priority
Cancel the low noise level control if
capacity is required while low noise
29
operation or night-time low noise
operation is in progress.
Demand 1
Used to make a change to the
setting
targeted power consumption level
when the demand 1 control signal
is inputted.
30
Demand 2
Used to use a targeted power
31
setting
current level when the demand 2
control signal is input.
Normal demand
Used to set permanent demand 1
32
setting
or 2 control without inputting any
external signal.
Indoor fan tap
Indoor fan speed is limited to L tap
setting
depending on connection capacity.
34
Height
In case the outdoor unit is installed
difference
in the lowest position and the
35
setting
height difference between the
highest indoor unit and the outdoor
unit exceeds 130 ft. (40 m),
Heat pump
Used for heat pump lockout
lockout 2
37
Emergency
To prohibit a compressor or
operation
complete in "Master". Since
38
(master)
module is permanent disabled,
immediately replace the defective
component(s).
Emergency
To prohibit a compressor or
operation (sub)
complete "sub 1". Since module is
39
permanent disabled, immediately
replace the defective
component(s).
Outdoor fan
Outdoor fan noise countermeasure
42
(limit fan speed).
191
Description
SEG
1
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
Level 1
2
5
Level 2
Level 3
About 8:00 PM
About 10:00 PM
2
6
About 12:00 AM
About 6:00 AM
About 7:00 AM
2
7
About 8:00 AM
OFF
ON (10 Hz)
2
8
OFF
ON
2
9
Level 1 (60%)
Level 2 (65%)
Level 3 (70%)
Level 4 (75%)
3
0
Level 5 (80%)
Level 6 (85%)
Level 7 (90%)
Level 8 (95%)
Level 1 (40%)
3
1
Level 2 (50%)
Level 3 (55%)
OFF
3
2
Demand 1 (2-30)
Demand 2 (2-31)
Indoor capacity ≥ 130%
Indoor capacity ≥ 130% in
3
4
heating
Remote controller setting (Not
limited)
Level > 40 m (130 ft)
Level max. 40 m (130 ft)
3
5
OFF
Mode 1
Mode 2
3
7
Mode 3
Mode 4
Mode 5
Mode 6
OFF
Master INV. 1 OFF
3
8
Master INV. 2 OFF
Master unit OFF
OFF
Sub INV. 1 OFF
3
9
Sub INV. 2 OFF
Sub unit OFF
Standard
4
2
Mode A
Mode B
Part 5 Field Settings and Test Operation
SiUS342303E
7 segment
display
Range
SEG
SEG
SEG
1
2
3
1
2
3
1
2
3
1
2
3
0
1
0
1
1
2
3
4
5
6
7
8
1
2
3
0
1
2
0
1
2
0
1
0
1
2
3
4
5
6
0
1
2
3
0
1
2
3
0
1
2