Field Setting from Outdoor Unit
 To activate the mild comfort setting under heating operation, change field setting [2-82] to 1.
• Eco
The original refrigerant temperature target, which is defined by the operation method (see above) is
kept without any correction, unless for protection control.
 To activate the eco comfort setting under cooling operation, change field setting [2-81] to 0.
 To activate the eco comfort setting under heating operation, change field setting [2-82] to 0.
No matter which control is selected, variations on the behavior of the system are still possible due
to protection controls to keep the unit operating under reliable conditions. The intentional target,
however, is fixed and will used to obtain the best balance between energy consumption and
comfort, depending on the application type.