Daikin VRV EMERION RXYQ-AATJA Service Manual page 37

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
Model name
Power supply
1 Cooling
Nominal
capacity
Rated
2 Heating
Nominal
capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Compressor Type
Volume
Number of
revolutions
Motor output ×
Number of units
Starting method
Fan
Type
Motor output ×
Number of units
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Gas pipe
Weight
Sound pressure level
(Reference data)
Sound power level
(Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Standard accessories
Drawing No.
Notes:
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Rated capacity is certified under AHRI standard 1230.
1.
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Rated capacity is certified under AHRI standard 1230.
2.
Part 1 General Information
RXYQ168AAYDA
3 phase, 460 V, 60 Hz
168,000 (49.2)
Btu/h
(kW)
160,000 (46.9)
189,000 (55.4)
Btu/h
(kW)
180,000 (52.8)
Ivory white (5Y7.5/1)
in. (mm)
65-3/8 × 48-13/16 × 30-1/8 (1,660 × 1,240 × 765)
Cross fin coil
Hermetically sealed scroll type
m³/h
r/min
6,504 + 6,204
kW
(3.97 + 6.46) × 1
Propeller fan
kW
cfm
9,935 (281.3)
(m³/min)
 5/8 (15.9) C1220T (brazing connection)
in. (mm)
 1-1/8 (28.6) C1220T (brazing connection)
in. (mm)
lbs (kg)
dB(A)
dB
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
%
lbs (kg)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
13.8 + 21
Soft start
0.65 × 2
Direct drive
761 (345)
65
85
Deicer
2-100
R-410A
25.8 (11.7)
4D144729
RXYQ192AAYDA
3 phase, 460 V, 60 Hz
192,000 (56.3)
184,000 (53.9)
216,000 (63.3)
206,000 (60.4)
Ivory white (5Y7.5/1)
65-3/8 × 68-7/8 × 30-1/8 (1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
19.1 + 20.1
5,628 + 5,934
(5.86 + 6.18) × 1
Soft start
Propeller fan
0.95 × 2
13,665 (386.9)
Direct drive
 5/8 (15.9) C1220T (brazing connection)
 1-1/8 (28.6) C1220T (brazing connection)
915 (415)
67
88
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
Deicer
4-100
R-410A
25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
4D144729
Specifications