Refrigerant Circuit (Piping Diagrams)
No. in
Electric
piping
symbol
diagram
Thermistor (Heat exchanger left deicer)
(34)
R10T
(Only for 192-240 class)
Thermistor (Heat exchanger right gas
(35)
R11T
pipe) (Only for 192-240 class)
Thermistor (Heat exchanger left gas pipe)
(36)
R12T
(Only for 192-240 class)
Thermistor
(37)
R13T
(M1C discharge pipe for 96-240 class)
Thermistor
(38)
R14T
(M1C compressor body for 96-240 class)
Thermistor
(39)
R15T
(M1C discharge pipe for 72 class,
M2C discharge pipe for 96-240 class)
Thermistor
(40)
R16T
(M1C compressor body for 72 class,
M2C compressor body for 96-240 class)
(41)
R17T
Thermistor (Box air)
39
Name
Used to detect liquid pipe temperature of air heat exchanger. Used
to make judgements on defrost operation.
This detects temperature of gas pipe for air heat exchanger.
Used to detect discharge pipe temperature.
Detects compressor surface temperature, this switch is activated at
surface temperature of 120°C (248°F) or more to stop the
compressor.
Used to detect discharge pipe temperature.
Detects compressor surface temperature, this switch is activated at
surface temperature of 120°C (248°F) or more to stop the
compressor.
Detects the air temperature inside the electrical component box.
SiUS342303E
Function
Part 2 Refrigerant Circuit