Daikin VRV EMERION RXYQ-AATJA Service Manual page 194

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Field Setting from Outdoor Unit
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
 Changing and access the setting in mode 2:
Once mode 2 is selected (press the MODE (BS1) button for more than 5 seconds), you can select
the wanted setting. It is done by pressing the SET (BS2) button.
Accessing the selected setting's value is done by pressing the RETURN (BS3) button once.
 To quit and return to the initial status, press the MODE (BS1) button.
 Changing the value of the selected setting in mode 2:
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor
unit's fan).
Mode: 2
Setting: 18
Make sure the segment indication is as during normal operation (default situation when shipped
from factory).
 Press the MODE (BS1) button for over 5 seconds; result segment display:
 Press the SET (BS2) button 18 times; result segment display:
 Press the RETURN (BS3) button once; the value which is returned (depending on the actual
Result: mode 2 setting 18 is addressed and selected, return value is the current setting situation.
 To change the value of the setting, press the SET (BS2) button until the required value appears
 To leave the field setting, press the MODE (BS1) button once, you will return to the default
187
 Once mode 2 is selected (press the MODE (BS1) button for more than 5 seconds) you can
select the wanted setting. It is done by pressing the SET (BS2) button.
 Accessing the selected setting's value is done by pressing the RETURN (BS3) button once.
 Now the SET (BS2) button is used to select the required value of the selected setting.
 When the required value is selected, you can define the change of value by pressing the
RETURN (BS3) button once.
 Press the RETURN (BS3) button again to start operation according to the chosen value.
Result: mode 2 setting 18 is addressed.
field situation), is the status of the setting. In the case of [2-18], default value is "0", which
means the function is not active.
on the segment indication. When achieved, define the setting value by pressing the RETURN
(BS3) button once. To start operation according to the chosen setting, confirm again by
pressing the RETURN (BS3) button.
situation when shipped from factory.
Result: mode 2 accessed.
Part 5 Field Settings and Test Operation
SiUS342303E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion rxyq-aayda

Table of Contents