Field Settings for Indoor Unit
1.4.40 Access Permission Level Setting
For BRC1E73 only
There are 2 levels as follows:
1.4.41 Remote Controller Thermostat Offset
For BRC1E73 only
First
Mode
Setting
Code
No.
Contents
01
No.
Main RC,
10
Auto mode
Sub RC,
11
Auto mode
Main RC,
12
Cool mode
−5.4°F
1c
(−3.0°C)
Main RC,
13
Heat mode
Sub RC,
14
Cool mode
Sub RC,
15
Heat mode
Note(s)
If different offset values are set for cooling and heating modes, the following issues may occur in
auto operation mode:
The indoor unit may switch more frequently between cooling/heating modes
The indoor unit may switch less frequently between cooling/heating modes
Setback on/off may happen more frequently
Setback on/off may happen less frequently
To avoid these issues, set the offset values for auto mode.
177
Level 2: The following buttons are selectable to be disable or enable.
Level 3: No buttons are selectable and only On/Off button is available.
Button
On/Off
Mode
Fan Speed
Menu/OK
Cancel
Mode No.
First Code No.
1c
3
02
03
04
−4.5°F
−3.6°F
−2.7°F
(−2.5°C)
(−2.0°C)
(−1.5°C)
Level 2
Selectable (Enable)
Selectable (Enable)
Selectable (Enable)
Selectable (Disable)
Unselectable (Disable)
Unselectable (Disable)
Second Code No.
01
02
Second Code No.
05
06
07
±0.0°F
−1.8°F
−0.9°F
0.9°F
(±0.0°C)
(−1.0°C)
(−0.5°C)
(0.5°C)
Level 3
Unselectable (Disable)
Unselectable (Enable)
Unselectable (Disable)
Unselectable (Disable)
Unselectable (Disable)
Unselectable (Disable)
( ) shows the factory setting.
: Factory setting
Contents
Level 2
Level 3
: Factory setting
08
09
10
11
1.8°F
2.7°F
3.6°F
(1.0°C)
(1.5°C)
(2.0°C)
Part 5 Field Settings and Test Operation
SiUS342303E
12
13
4.5°F
5.4°F
(2.5°C)
(3.0°C)