SiUS342303E
The set temperature displayed on the remote controller remains the same even if the target
As soon as people are detected while the temperature is shifted, this control will be cancelled
1.4.6 Auxiliary Electric Heater ON/OFF Temperature
Note(s)
1. S value varies automatically based on the room temperature trend.
FXFQ-T, FXMQ-PB
Mode
11 (21)
FXZQ-TB, FXUQ-PA, FXEQ-P, FXSQ-TB, FXMQ-TB, FXLQ-M, FXNQ-M, FXTQ-TA
Mode
11 (21)
Part 5 Field Settings and Test Operation
(°F)
87.8
86
84.2
82.4
80.6
78.8
69.8
68
66.2
64.4
62.2
temperature is shifted.
(reset).
Thermostat
ON
First Code No. Symbol
No.
Ton
1
Toff
First Code No. Symbol
No.
1
Ton
2
Toff
State of absence
(°C)
31
30
29
28
27
Cooling (at 28°C (82.4°F))
26
21
Heating (at 20°C (68°F))
20
19
18
17
30 (60)
60 (120)
Elapsed time of absence (min.)
The values in parentheses represent the time
when Second code No. is 02.
Set temperature
Toff + S (∗1)
Ton + S (∗1)
Second Code No.
01
02
03
–4°C
–3.5°C
–3°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
–1°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
Second Code No.
01
02
03
–4°C
–3.5°C
–3°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
–1°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
Field Settings for Indoor Unit
Detection
Thermostat
OFF
: Factory setting
04
05
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
–0.5°C
0°C (0°F)
(–0.9°F)
: Factory setting
04
05
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
(–2.7°F)
–0.5°C
0°C
(–0.9°F)
(0°F)
06
–1.5°C
(–2.7°F)
0.5°C
(0.9°F)
06
–1.5°C
0.5°C
(0.9°F)
164