SiUS342303E
2.4.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
1
COOL/HEAT
Several systems as 1 zone change
selection
over COOL/HEAT:
 INDIVIDUAL: VRV indoor unit or
A-B-C input set mode.
0
 MASTER: System is the
COOL/HEAT master unit.
 SUB: System is not a
COOL/HEAT master.
COOL/HEAT
Used to make address setting for
1
unified address
unified cooling/heating operation.
Low noise/
Used to make address setting for
2
demand address
low noise/demand operation.
Phased
Used to make setting for phased
4
installation
installation.
setting
Indoor fan forced
Used to force the fan of indoor unit
5
H
to H tap.
Forced
Used to force all indoor units to
6
thermostat
operate forced thermostat ON.
Te setting
Used to make setting of targeted
(Cooling
evaporating temperature for
operation)
cooling operation.
8
Tc setting
Used to make setting of targeted
condensing temperature for
9
heating operation.
Eco setting is available from an external input.
When this configuration is set, it is not possible to turn
the Eco refrigerant control ON/OFF using the remote
11
controller. Also, depending on the settings, low noise
operation or demand operation may not be performed
using the external control adaptor.
External low
Used to receive external low noise
12
noise setting/
or demand signal.
demand setting
AIRNET address Used to set address of AIRNET.
13
Heat pump
Used for heat pump lockout.
16
lockout 1
High ESP setting
Fan high static pressure setting
18
FAN
Additional
Used to perform additional
20
refrigerant
refrigerant charging operation
charge
(compressor operation).
Refrigerant
Used to set the system to
21
recovery and
refrigerant recovery mode (without
vacuuming
compressor run).
Automatic night-
Automatic night-time low noise
time low noise
operation.
22
operation
Time for the operation is subject to
the start and end time settings.
Used to set Eco mode invalid.
When this configuration is set, it is not possible to turn
23
the Eco mode ON/OFF using the external control
adaptor.
Part 5 Field Settings and Test Operation
Description
SEG
1
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
Individual
Unified Master
Unified Sub
0
0
Address:
0
1
0 ~
31
Address:
0
2
0 ~
31
Normal installation
0
4
Single module to dual module
installation
Normal operation
0
5
Indoor fan H
Normal operation
0
6
Forced thermostat ON
Auto
6°C (43°F)
7°C (45°F)
0
8
8°C (46°F)
9°C (48°F)
10°C (50°F)
11°C (52°F)
Auto
41°C (106°F)
0
9
43°C (109°F)
46°C (115°F)
Unavailable
Eco setting by low noise level
input
1
1
Eco setting by demand input
Input LNO/DE
1
2
OFF
ON
Address:
1
3
0 ~
63
OFF
1
6
ON
OFF
1
8
ON
OFF
2
0
Refrigerant charging ON
Refrigerant recovery
2
1
OFF
ON
OFF
Level 1
2
2
Level 2
Level 3
Valid
Invalid for cooling
2
3
Invalid for heating
Invalid for cooling and heating
Field Setting from Outdoor Unit
7 segment
display
Range
SEG
SEG
1
2
3
3
6
SEG
3
0
1
2
0
1
0
1
0
1
0
1
0
1
0
2
3
4
5
6
7
0
1
3
6
0
1
2
0
1
0
3
0
1
0
1
0
1
0
1
0
1
2
3
0
1
2
3
190