Outdoor Unit Main/Sub Pcb Abnormality - Daikin VRV EMERION RXYQ-AATJA Service Manual

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Troubleshooting by Error Code

3.32 Outdoor Unit Main/Sub PCB Abnormality

Applicable
All outdoor unit models
Models
E1
Error Code
Method of Error
Abnormality is detected under the communication conditions in the hardware section between the
Detection
indoor unit and outdoor unit.
Error Decision
When the communication conditions in the hardware section between the indoor unit and the
Conditions
outdoor unit are not normal.
Supposed
 Defective outdoor unit main PCB (A1P)
Causes
 Defective outdoor unit sub PCB (A8P)
 Defective connection communication line between indoor and outdoor units
Troubleshooting
299
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn OFF the power once
and turn ON again.
Return to normal?
NO
Check if
inside/outdoor relay
wires of outdoor unit main/sub
PCB is disconnected.
NO
Does the error
code show E1-08/09?
NO
YES
YES
YES
SiUS342303E
External factor other than error (for
example, noise etc.).
Connect the communication line
correctly.
Replace the outdoor unit sub PCB
(A8P).
Replace the outdoor unit main PCB
(A1P).
Part 6 Service Diagnosis