Daikin VRV EMERION RXYQ-AATJA Service Manual page 179

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
FXZQ-TB, FXEQ-P
Mode
13 (23)
FXHQ-M, FXAQ-P
Mode
13 (23)
1.4.23 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of
air discharge outlet has been installed.) The second code No. is factory set to 01.
Mode
13 (23)
1.4.24 Swing Pattern Settings (For units with the infrared floor sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side
by side are set to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Mode
13 (23)
1.4.25 Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Mode
13 (23)
Part 5 Field Settings and Test Operation
First Code
Second
No.
No.
Code No.
01
0
02
03
First Code
Second
No.
No.
Code No.
01
0
02
03
First Code
Second
No.
No.
Code No.
01
1
02
03
First Code
Second Code
No.
No.
No.
01
2
02
03
First Code
Second Code
No.
No.
No.
01
4
02
03
Contents
Standard
Lower than 2.7 m (8-3/4 ft)
High Ceiling 1
Higher Ceiling 2
Ceiling height
Slight increase
Normal increase
F: 4-direction airflow
T: 3-direction airflow
W: 2-direction airflow
All direction synchronized swing
Facing swing
Upward (Draft prevention)
Downward (Ceiling soiling prevention)
Field Settings for Indoor Unit
: Factory setting
Ceiling height
Lower than 3.0 m (10 ft)
Lower than 3.5 m (11-1/2 ft)
: Factory setting
Standard
: Factory setting
Ceiling height
: Factory setting
Contents
: Factory setting
Contents
Standard
172