SiUS342303E
Error code
J6 - 01
Defective heat exchanger deicer thermistor (R3T) (Master) Refer to the J6 flowchart and make a diagnosis of the
J6 - 02
Defective heat exchanger deicer thermistor (R3T) (Sub)
Defective heat exchanger right gas pipe thermistor (R11T)
J6 - 08
(Master)
Defective heat exchanger right gas pipe thermistor (R11T)
J6 - 09
(Sub)
Defective heat exchanger left gas pipe thermistor (R12T)
J6 - 11
(Master)
Defective heat exchanger left gas pipe thermistor (R12T)
J6 - 12
(Sub)
Defective heat exchanger left deicer thermistor (R10T)
J6 - 22
(Master)
Defective heat exchanger left deicer thermistor (R10T)
J6 - 23
(Sub)
J7 - 06
Defective subcooling liquid pipe thermistor (R8T) (Master)
J7 - 07
Defective subcooling liquid pipe thermistor (R8T) (Sub)
J7 - 17
Standby for preventing fusible plug removal
J7 - 18
Defective subcooling injection thermistor (R7T) (Master)
J7 - 19
Defective subcooling injection thermistor (R7T) (Sub)
Defective heat exchanger liquid pipe thermistor (R2T)
J8 - 01
(Master)
Defective heat exchanger liquid pipe thermistor (R2T)
J8 - 02
(Sub)
Defective heat exchanger left liquid pipe thermistor (R9T)
J8 - 08
(Master)
Defective heat exchanger left liquid pipe thermistor (R9T)
J8 - 09
(Sub)
J9 - 01
Defective subcooling gas pipe thermistor (R6T) (Master)
J9 - 02
Defective subcooling gas pipe thermistor (R6T) (Sub)
J9 - 17
Defective electrical box air outlet thermistor (R4T) (Master)
J9 - 18
Defective electrical box air outlet thermistor (R4T) (Sub)
JA - 06
Defective high pressure sensor (S1NPH): Open (Master)
JA - 07
Defective high pressure sensor (S1NPH): Short (Master)
JA - 08
Defective high pressure sensor (S1NPH): Open (Sub)
JA - 09
Defective high pressure sensor (S1NPH): Short (Sub)
JC - 06
Defective low pressure sensor (S1NPL): Open (Master)
JC - 07
Defective low pressure sensor (S1NPL): Short (Master)
JC - 08
Defective low pressure sensor (S1NPL): Open (Sub)
JC - 09
Defective low pressure sensor (S1NPL): Short (Sub)
Part 6 Service Diagnosis
Error Description
Troubleshooting
relevant thermistor of the relevant unit based on the Error
code shown to the left.
Refer to the J7 flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the Error
code shown to the left.
Refer to the J8 flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the Error
code shown to the left.
Refer to the J9 flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the Error
code shown to the left.
Refer to the JA flowchart and make a diagnosis of the
relevant sensor based on the Error code shown to the left.
Refer to the JC flowchart and make a diagnosis of the
relevant sensor based on the Error code shown to the left.
Troubleshooting by Error Code
Diagnosis
240