Field Settings for Indoor Unit
1.4.26 Setting of Static Pressure Selection (for FXDQ-M models)
Mode No.
1.4.27 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment (11 (21)-7),
or manually using external static pressure settings (13 (23)-6).
FXMQ-PB models
The Second Code No. is set to 02 for FXMQ07/09/12PB, and 07 for FXMQ15/18/24/30/36/48/54PB
at factory setting.
1. FXMQ15/18/24/30/36/48PB cannot be set to 30 Pa (0.12 inWG).
2. FXMQ07/09/12PB cannot be set to 110-200 Pa (0.44-0.80 inWG).
3. FXMQ54PB cannot be set to 30 Pa (0.12 inWG) or 150-200 Pa (0.60-0.80 inWG).
FXSQ-TB models
1. FXSQ18-48TB cannot be set to 30-40 Pa (0.12-0.16 inWG).
2. FXSQ54TB cannot be set to 30-40 Pa (0.12-0.16 inWG) or 150 Pa (0.60 inWG).
173
First Code No.
Second Code No.
13 (23)
5
Mode No.
First Code No.
13 (23)
6
Mode No.
First Code No.
13 (23)
6
Standard (FXDQ07-12M: 10 Pa (0.04 inWG),
01
FXDQ18/24M: 30 Pa (0.12 inWG))
High static pressure (FXDQ07-12M: 15 Pa (0.06 inWG),
02
FXDQ18/24M: 45 Pa (0.18 inWG))
Second Code No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Second Code No.
03
04
05
06
07
08
09
10
11
12
13
14
15
SiUS342303E
: Factory setting
Contents
: Factory setting
Contents
30 Pa (0.12 inWG) (1) (3)
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG) (2)
120 Pa (0.48 inWG) (2)
130 Pa (0.52 inWG) (2)
140 Pa (0.56 inWG) (2)
150 Pa (0.60 inWG) (2) (3)
160 Pa (0.64 inWG) (2) (3)
180 Pa (0.72 inWG) (2) (3)
200 Pa (0.80 inWG) (2) (3)
: Factory setting
Contents
30 Pa (0.12 inWG) (1) (2)
40 Pa (0.16 inWG) (1) (2)
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG)
120 Pa (0.48 inWG)
130 Pa (0.52 inWG)
140 Pa (0.56 inWG)
150 Pa (0.60 inWG) (2)
Part 5 Field Settings and Test Operation