A9" Electronic Expansion Valve Malfunction / Dust Clogging - Daikin RTSQ20PY1 Service Manual

Vrv iii-c r-410a heat pump 50hz
Hide thumbs Also See for RTSQ20PY1:
Table of Contents

Advertisement

SiBE31-801_C
A9
4.6
"
" Electronic Expansion Valve Malfunction / Dust
Clogging
A9
Remote
Controller
Display
Applicable
FXFQ25~125P
Models
Method of
Check coil condition of electronic expansion valve by using micro-computer.
Check dust clogging condition of electronic expansion valve main body by using micro-
Malfunction
computer.
Detection
Malfunction
Pin input for electronic expansion valve coil is abnormal when initializing micro-computer.
Either of the following conditions is seen/caused/ occurs while the unit stops operation.
Decision
Conditions
Supposed
Causes
Troubleshooting
Temperature of suction air (R1T) – temperature of liquid pipe of heat exchanger (R2T)>8°C
Temperature of liquid pipe of heat exchanger (R2T) shows fixed degrees or below.
Defective drive of electronic expansion valve
Defective PCB of indoor unit
Defective relay cables