Check
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
5.8

Rotation Pulse Check on the Outdoor Unit PCB

Check No.16
Outdoor fan motor
 09/12 class
Check if the sinusoidal voltage is generated between pins 1 - 3 and 3 - 5 when the fan motor is
manually rotated once.
 18/24 class
Make sure that the voltage of 320 ± 30 V is applied.
1. Set operation OFF and power OFF. Disconnect the connector S70.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 6.5 VDC.
5. Keep operation OFF and power OFF. Connect the connector S70.
6. Check whether 4 pulses (0 ~ 15 VDC) are output at the pins 1 - 4 when the fan motor is rotated
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2  Defective PCB  Replace the outdoor unit PCB (main PCB).
If NG in step 4  Defective Hall IC  Replace the outdoor fan motor.
If OK in both steps 2 and 4  Replace the outdoor unit PCB (main PCB).
140
Otherwise, the terminals may be burned due to loosening.
1 turn by hand.
Direction of crimp
FASTON terminal
PCB
S70
5
Phase W
3
Phase V
1
Phase U
SiUS042113E
This size is shortened
by the crimp.
(R15292)
Part 6 Service Diagnosis