High Calibration Point (2.3.2.); Sensor Offset (2.3.3.); Rate (2.4.); Response Rate (2.4.1.) - Siemens SITRANS LR200 7ML5422 Operating Instructions Manual

Radar transmitter with ma/hart
Table of Contents

Advertisement

7.2.2.2

High calibration point (2.3.2.)

Description
Values
Factory setting
Related
parameters
The value produced by the echo processing which represents the distance from sensor
1)
reference point to the target. For more details, refer to Sensor mode (2.2.2.) (Page 99).
Note
When setting the High Calibration Point value, echoes are ignored within Near Range. For
details, refer to Near range (2.8.1.) (Page 110).
7.2.2.3

Sensor offset (2.3.3.)

Description
Values
Factory setting
Related parame-
ters
The value produced by the echo processing which represents the distance from sensor
reference point to the target. Refer to Sensor mode (2.2.2.) (Page 99) for an illustration.
7.2.3

Rate (2.4.)

7.2.3.1

Response rate (2.4.1.)

Response Rate sets the reaction speed of the device to measurement changes. Use a
setting just faster than the maximum filling or emptying rate (whichever is greater).
Note
Changing Response Rate resets Fill rate/min (2.4.2.) (Page 102), Empty rate/min (2.4.3.)
(Page 102) and Damping filter (2.2.4.) (Page 100).
Response rate
slow (factory setting)
medium
fast
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
Distance from sensor reference point
fined in Units (2.2.1.).
0 to 20 m
0.00 m
Units (2.2.1.) (Page 99)
Near range (2.8.1.) (Page 110)
Sensor Offset is a constant offset that can be added to or subtracted from sen-
sor value
to compensate if the sensor reference point has shifted. For example,
1)
this could result from adding a thicker gasket or reducing the standoff/nozzle
height. The units are defined in Units (2.2.1.) (Page 99).
-99.999 to +99.999
0.00
Units (2.2.1.) (Page 99)
Fill rate/min (2.4.2.)
(Page 102)
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
to High Calibration Point. Units are de-
1)
Empty rate/min (2.4.3.)
(Page 102)
Damping filter (2.2.4.)
(Page 100)
10 s
10 s
0 s