Rate (2.3.6.) - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters (foundation fieldbus)
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

8.2.3.6

RATE (2.3.6.)

RESPONSE RATE (2.3.6.1.)
Changing Response Rate resets
FILL RATE/MIN (2.3.6.2.) (Page 126)
EMPTY RATE/MIN (2.3.6.3.) (Page 126)
AVERAGE AMOUNT (2.8.3.) (Page 141)
Factory setting:
Setting range:
Purpose:
Description:
Related
parameters:
It may be necessary to reduce this further for FAST applications.
a)
● Use a setting just faster than the maximum filling or emptying rate (whichever is faster).
● For the measurement value update time, see "Update time" in Performance (Page 171).
LR560 (FOUNDATION FIELDBUS)
Operating Instructions, 06/2018, A5E34648692-AE
Medium
Response
FILL RATE/MIN (2.3.6.2.)
rate
(Page
126)/EMPTY RATE/MIN
(2.3.6.3.)
(Page 126)
Slow
0.1 m/min (0.32 ft/min)
Medium
1.0 m/min (3.28 ft/min)
Fast
10.0 m/min (32.8 ft/min)
Sets the reaction speed of the device to measurement
changes.
Use a setting just faster than the maximum filling or emptying
rate (whichever is faster).
FILL RATE/MIN (2.3.6.2.) (Page 126)
EMPTY RATE/MIN (2.3.6.3.) (Page 126)
AVERAGE AMOUNT (2.8.3.) (Page 141)
FILTER TIME CONSTANT (2.5.7.1.) (Page 140)
Parameter Reference
8.2 SETUP (2.)
FILTER TIME
AVERAGE
CONSTANT
AMOUNT
(2.5.7.1.)
(2.8.3.)
(Page 140)
(Page 141)
600 s
0.9
60 s
0.75
0 s
0.75