Install an ACX7100-32C DC Power Supply Module

WARNING: Before performing DC power procedures, ensure that power is removed
from the DC circuit. To ensure that all power is off, locate the circuit breaker on the
panel board that services the DC circuit, switch the circuit breaker to the off position,
and tape the switch handle of the circuit breaker in the off position.
To install a DC PSM (see
1.
Ensure that the voltage across the DC power source cable leads is 0 V and that there is no chance
that the cable leads might become active during installation.
2.
Wrap and fasten one end of the ESD grounding strap around your bare wrist, and connect the
other end of the strap to the ESD point on the chassis.
3.
Using both hands, slide the DC PSM straight into the slot on the rear panel of the chassis until the
PSM is fully seated in the slot. The PSM faceplate must align with any adjacent PSM faceplate
installed in the power supply slot.
4.
Remove the clear plastic cover protecting the terminals on the faceplate.
5.
Remove the screws from the terminals.
6.
Secure each power cable lug to the terminal with the screw (see
overtighten the screw.
a. Secure the positive (+) DC source power cable lug to the RTN (return) terminal.
b. Secure the negative (–) DC source power cable lug to the –48V (input) terminal.
CAUTION:
• You must ensure that power connections maintain the proper polarity. The
power source cables might be labeled (+) and (–) to indicate their polarity. There
is no standard color coding for DC power cables. The color coding used by the
external DC power source at your site determines the color coding for the leads
on the power cables that attach to the terminal studs on each PSM.
• Ensure that each power cable lug seats flush against the surface of the terminal
block as you are tightening the screws. Ensure that each screw is properly
threaded into the terminal. Applying installation torque to the screw when
improperly threaded can result in damage to the terminal.
7.
Replace the clear plastic cover over the terminals on the faceplate.
8.
Verify that the power cabling is correct, that the cables do not touch or block access to router
components, and that they do not drape where people could trip over them.
Figure 41 on page
94):
Figure 42 on page
94). Do not
93