Panasonic WH-ADF0309J3E5CM Service Manual page 245

Table of Contents

Advertisement

Diagnosis
display
Abnormality
(Indoor
or
model:
protection
CS-XX /
control
S-XX /
WH-XX)
H36 / F23 /
Outdoor gas pipe
H51
temperature
sensor
abnormality
H37 / F24 /
Outdoor liquid
H53
pipe temperature
sensor
abnormality
H64 / P04 /
Outdoor high
F27
pressure sensor
abnormality
H89 / F16 /
Compressor
H64
discharge
temperature
sensor
abnormality
H97 / P22 /
Outdoor fan motor
F15
mechanism lock
H98 / - /
Indoor high
H98
pressure
protection
H99 / - /
Indoor operating
H99
unit freeze
protection
H64
Outdoor high
pressure switch
abnormality
H89
High pressure
sensor abnormal
F11 / L18 /
4-way valve
F25
switching
abnormality
F17 / P14 /
Indoor standby
F33
units freezing
abnormality
F90 / H02 /
Power factor
F41
correction (PFC)
circuit protection
F91 / P15 /
Refrigeration
F24
cycle abnormality
LED
LED
LED
LED
LED
6
5
4
3
LED
Abnormality
Protection
2
1
judgement
operation
Continuous
Heating
for 5s
protection
operation
only
Continuous
Cooling
for 5s
protection
operation
only
Continuous
for 1
minute
4 times
happens
within 20
minutes
2 times
happen
within 30
minutes
-
-
-
-
4 times
happen
within 30
minutes
3 times
happen
within 40
minutes
4 times
happen
within 20
minutes
4 times
happen
within 60
minutes
245
Problem
Outdoor gas pipe
temperature
sensor open or
short circuit
Outdoor liquid
pipe temperature
sensor open or
short circuit
-
High pressure
sensor open
circuit during
compressor stop
-
High pressure
sensor open or
short circuit
-
Outdoor fan motor
lock or feedback
abnormal
-
Indoor high
pressure
protection
(Heating)
-
Indoor freeze
protection
(Cooling)
-
High pressure
switch open circuit
during
compressor stop
-
High pressure
sensor open or
short circuit
-
4-way valve
switching
abnormal
-
Wrong wiring and
connecting pipe,
expansion valve
leakage.
-
Power factor
correction circuit
abnormal
-
Refrigeration
cycle abnormal
Check location
 Outdoor gas
pipe
temperature
sensor lead wire
and connector
 Outdoor liquid
pipe
temperature
sensor lead wire
and connector
 High pressure
sensor
 Lead wire and
connector
 High pressure
sensor
 Lead wire and
connector
 Outdoor fan
motor lead wire
and connector
 Fan motor lock
or block
 Check indoor
heat exchanger
 Air filter dirty
 Air circulation
short circuit
 Check indoor
heat exchanger
 Air filter dirty
 Air circulation
short circuit
 High pressure
switch lead wire,
connector
CN-PSW1
 High pressure
sensor lead
wire, connector
CN-HPS
 4-way valve
 Lead wire and
connector.
 Check
indoor/outdoor
connection wire
and pipe
 Indoor heat
exchanger
sensor lead wire
and connector
 Expansion valve
lead wire and
connector.
 Outdoor PCB
faulty
 Insufficient
refrigerant or
valve close