ON:
Blinking:
OFF:
Wireless remote
controller
receiver display
Abnormal
display
P15
P16
Operating
and standby
lamp blinking
P22
alternately
P29
P31
Alarm contents
Insufficient gas level detected
Compressor overcurrent trouble
Outdoor unit fan motor trouble
Outdoor unit fan trouble
Inverter compressor trouble
Indoor unit in group control trouble
238
Error location
Check the refrigerant cycle (gas leak)
Trouble with the electronic expansion valve
Valve (or refrigerant circuit) blockage
Layer short on the compressor
Compressor locked
Check the outdoor unit control PCB
Check the outdoor unit fan motor, connector
Layer short on the compressor
Check the outdoor unit control PCB
Check the inverter compressor wiring (Open
phase/Reverse phase)
Compressor actuation failure (include lock)
Valve (or refrigerant circuit) blockage
Repair indoor unit which blinking alarm