20.1.3
Power Save Mode
Power Save Mode can be enabled by pushing POWER SAVE switch (SW4) to ON before power supply ON.
When Power Save Mode is ON, the unit can be operate at lower running current where the breaker capacity not
achieve the requirement.
20.1.4
Mode priority function
Mode priority function can be enabled by pushing MODE PRIORITY switch (SW5) to ON before power supply
ON.
When Mode Priority Function is ON, the mode priority is given to higher capacity indoor units.
20.1.5
Cooling only function
The unit capable to limit the operation mode to Cooling Mode only (Heating mode disabled) by cutting JP1
(COOL ONLY) before power supply ON.
This function prevent wrong operation during the unit installed in server room.
This function could be disabled again by short the JP1 (COOL ONLY) before power supply ON.
However, tank heating operation is still allowed even if the cooling only function is set.