13.2 Select The Best Location

13.2.1
Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Refrigerant piping size
Outdoor Unit
Liquid - side
Gas - side
Outdoor Unit
Pre-charged refrigerant
Maximum total piping length for additional gas
Additional refrigerant
Rated length (m)
Allowable piping length of each indoor unit (min-max)
Allowable total piping length of all indoor unit
Height difference between indoor and outdoor unit
Height difference between indoor and outdoor unit
CU-2WZ71****
ø 6.35 t0.8
ø 12.7 t0.8
Refrigerant Amount and Allowable Piping Length
Indoor - Duct unit
Indoor - Tank unit
Outdoor unit located on upper side
Outdoor unit located otherwise
Outdoor unit located on upper side
Outdoor unit located otherwise
166
Outdoor Unit Installation Diagram
This illustration is for explanation purposes only.
Note:
*
Respective indoor unit installation procedure shall
refer to instruction manual provided in the indoor unit
packaging.
Installation parts you
should purchase ( )
It is advisable to avoid
more than 2 blockage
directions. For better
ventilation & multiple-
outdoor installation,
please consult
authorized dealer/
specialist.
Connection cable ( )
(To Tank and Duct unit)
Additional drain hose ( )
1/4" Liquid side piping ( )
1/2" Gas side piping ( )
CU-2WZ71****
2.4 kg
30 m
20 g/m
5 m
5 m
3 m ~ 35 m
70 m or less
30 m or less
15 m or less
15 m or less
30 m or less