12.1.9
Checklist after Installation Work
Work List
No.
Are the indoor units installed following the
Installation
1
content of the section "12.1.2. SELECTING
THE INSTALLATION SITE"?
Is the earth leakage circuit breaker (all-pole
2
switching function provided) installed?
Is there any wrong installation of optional parts
3
or wrong wiring?
4
Was the ground wire work performed?
Are there any wrong power supply wiring,
5
wrong connection wire, wrong signal wire or
loose screw?
6
Is the thickness of wire in accordance with rule?
Is the power-supply voltage equal to the
7
nameplate of the unit?
Was the check of the airtight test, flared tube
8
fitting and gas leakage on the welded portion
performed?
Has the adhesive been applied to the drain
9
connecting portion (resin portion) of the indoor
unit?
Drain
10
Is there water leakage?
Check
Indoor unit drain pipe has a downward gradient
11
(1/100 or more) by rule. Is the drain water
flowing smoothly?
Was the heat insulation work at a suitable
Heat
location including the flared tube fitting
12
Insulation
(refrigerant tube & drain pipe) performed
properly?
13
Did the abnormal sound occur?
Test Run
Did the cool and warm airflow discharge from
14
the indoor unit?
Content
125
Possibility of Failure & Checkpoint
Check
There is a possibility of light injure or loss of
property.
Power failure or short circuit may cause electric
shock or fire. Check installation work and
ground wire work.
If the gas leakage occurs, the unit quality not
only becomes inferior but affects environment.
Repair it as quickly as possible.
The resin portion cracks after a few months and
it may cause water drain.
Since there is a possibility of water drain, repair
the drain pipe if the drain failure or water drain
occurs.
The quality of unit not only becomes inferior but
there is a possibility of the water drain. So,
perform the heat insulation work properly.
Check if there is a fan contact or distortion of
the indoor unit.
Check if the unit does not operate or there is a
wrong tubing or wiring connection with another
system.