Technical Data (Wh-Adf0309J3E5Cm); Operation Characteristics; Heating Capacity Table - Panasonic WH-ADF0309J3E5CM Service Manual

Table of Contents

Advertisement

29. Technical Data (WH-ADF0309J3E5CM)

29.1 Operation Characteristics

Heating Characteristics at Different Outdoor Air Temperature
Condition
Outdoor air temperature : 7°C (DBT), 6°C (WBT)
Indoor water inlet temperature : 30°C
Indoor water outlet temperature : 35°C
Piping length : 7 m
8.200
7.500
6.800
6.100
5.400
4.700
-15-14-13-12-11-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12
2.400
2.200
2.000
1.800
1.600
1.400
-15-14-13-12-11-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12

29.2 Heating Capacity Table

Water Out (°C)
Outdoor Air (°C)
-15
-7
2
7
12
25
Capacity
Input Power
(W)
(W)
4850
2150
5400
1700
6500
1770
8160
1630
8220
1280
Outdoor Temperature (°C)
Outdoor Temperature (°C)
35
Capacity
Input Power
(W)
(W)
4750
2280
5600
1970
6700
2060
8000
1900
8000
1520
299
45
Capacity
Input Power
(W)
(W)
4650
2440
5600
2400
6600
2450
8000
2300
8000
2000
55
Capacity
Input Power
(W)
(W)
4500
3200
5300
2780
6000
2890
8000
2850
8000
2600

Advertisement