14.7 Tank Heater Control

14.7.1
Tank Heater Remote Control Setting
1
Tank heater selection:
Internal: - Backup Heater use to heat up tank when select internal
Heater Delay ON Timer need to set. (range 20 min ~ 3 hrs)
2
Tank Heater ON/OFF selection by user.
The remote control Tank set Temperature range will change according to the External and Internal Tank Heater use.
14.7.2
Internal Heater Control at Tank Mode
Internal heater turn ON condition:
1
Internal Heater select for Tank heater by remote controller
2
Tank Heater select ON by user.
3
Backup Heater Enable
4
Tank Temperature < Tank Set Temperature
5
Tank Thermo ON for remote controller set timer
6
20 minutes from previous heater off.
Room heater turn OFF condition:
1
Tank Temperature > Tank Set Temperature + [0°C] for continuous 15 seconds. OR
2
Mode Change or Operation OFF by remote controller OR
* Backup Heater Turn ON/OFF all together according to the selected heater capacity.
Tank Heater Selection
Internal
Tank
Temp.
65°C
Tank Water Set Temp
Range
40 ~ 65°C
Heat Pump
Operation
188
Backup
Heater
Operation
Time